Removing and installing the power terminal block – Rockwell Automation 2711-M3A18L1_M3A19L1 PanelView 300 Micro Terminals Installation Instructions User Manual

Page 11

Advertising
background image

PanelView 300 Micro Terminal 11

41061-156-01(A)

To connect DC power to the PanelView 300 Micro terminal:

1. Secure the DC power wires to the screw terminal block.

2. Secure the Functional Earth Ground wire to the screw terminal block.

3. Apply power (24V dc nominal) to the terminal.

Removing and Installing the Power Terminal Block

You can remove and re-install the power terminal block for ease of installation,
wiring and maintenance. The terminal block is pre-installed when shipped.
Additional terminal blocks (quantity of 10) are available by ordering Catalog
Number 2711-TBDC.

To remove the DC power terminal block:

1. Disconnect all electrical power from the panel. See Explosion Hazard Warning

above.

2. Insert tip of small flat-blade screw driver into DC power terminal access slot.

!

DANGER

Explosion Hazard

• Substitution of components may impair suitability for Class

I, Division 2.

• Do not disconnect equipment unless power has been

switched off and area is known to be non-hazardous.

• Do not connect or disconnect components unless power has

been switched off.

• All wiring must comply with N.E.C. article 501-4(b).

Functional Earth Ground

+

DC Positive

-

DC Negative

Advertising