Using the Communications Port

The PanelView 300 Micro terminal is available in 2 versions.

Both versions have an identical RS-232 communications port with a MicroLogix
8-pin mini-DIN style connector. The only difference is the protocol firmware
(DF1 or DH485) pre-loaded at the factory. Both versions of the protocol
firmware are supplied with the PanelBuilder32 software. You can change the
protocol by downloading the firmware to the terminal using the Windows
PanelView MotherBoard Firmware Download Utility (WinMBFWDL) utility.
This utility is included with the PanelBuilder32 software.

The following table lists the communication parameters supported by each of the
protocols on the RS-232 communications port.

Catalog Number

Communication Port

Communication Protocol

2711-M3A18L1

RS-232

DF1

2711-M3A19L1

RS-232

DH485

Communication Link

Communication Parameters

RS-232 or DH-485 Link Point-to-Point
Baud Rate:
Maximum Distance

1200, 2400, 9600, 19.2K Baud
6.1 meters (20 feet)

DF1 - Full Duplex Communication
Baud Rate
Maximum Distance

1200, 2400, 4800, 9600, 19.2K Baud
15.24 meters (50 feet)

Pin #

Signal

1

NC (No Connection)

2

GND

3

RTS

4

RXD

5

NC (No Connection)

6

CTS

7

TXD

8

GND

1

3

2

5

4

8

7

6

RS-232
8-pin mini-DIN
connector

Port is used for both
communications with a controller
and to transfer application files.