Wiring and Safety Guidelines

Install the PanelView 300 Micro terminal using publication 70E, Electrical
Safety Requirements for Employee Workplaces. In addition to the NFPA general
guidelines, follow these recommendations:

• Route incoming power to the PanelView 300 Micro by a separate path from

the communication cable.

• Where power and communication lines must cross, they should cross at right

angles. Communication lines can be installed in the same conduit as low level
DC I/O lines (less than 10 Volts).

• Grounding minimizes noise from Electromagnetic Interference (EMI) and is a

safety measure in electrical installations. To avoid EMI, shield and ground
cables appropriately.

A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.

Mounting the Terminal

Enclosures

Mount the PanelView 300 Micro terminal in a panel or enclosure to protect the
internal circuitry. The terminal meets NEMA 12/13 and 4X (indoor use) ratings
only when properly mounted in a panel or enclosure with the equivalent rating.
Allow enough space within the enclosure for adequate ventilation. Consider heat
produced by other devices in the enclosure. The ambient temperature around the
PanelView 300 Micro must be between 0

°

and 55

°

C (32

°

and 131

°

F).

Make provisions for accessing the side panel of the terminal for wiring,
maintenance and troubleshooting.

Mounting Dimensions

133 mm

(5.23 in.)

111 mm

(4.38 in.)

48 mm

(1.87 in.)

35 mm

(1.39 in.)