Ladder logic updates to support visible states, Ladder logic updates to, Support visible states – Rockwell Automation Migrating PanelView Enhanced Terminal Applications User Manual
Page 86: Age 86, Ge 86

86
Publication 2711P-QS001A-EN-P - October 2007
Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
Ladder Logic Updates to
Support Visible States
Because the piloted control list selector uses an array tag, not
individual tags, to implement visible states, you need to make changes
to your ladder logic.
Follow these steps to update your ladder logic using RSLogix 5
software. The same steps would apply if using RSLogix 500 sofware.
1. Create a new data file.
2. Configure these parameters
for the data file.
a. Accept the File value.
b. Set the Type to Integer.
c. Enter a meaningful Name
for the file.
d. For Elements, enter the
number of visible states
in the original
PanelBuilder 1400e
cursor list object.
e. Click OK to save your
settings.
3. Right-click on Program Files
and select New to add a
new program file to the PLC
program.