Description of Adapter Input Status Word

The input status word consists of:

I/O module fault bits - 1 status bit for each slot

node address changed - 1 bit

The adapter input status word bit descriptions are shown in the
following table.

Bit
Description

Bit

Explanation

I/O Module
Fault

0

This bit is set (1) when an error is detected in slot
position 0.

1

This bit is set (1) when an error is detected in slot
position 1.

2

This bit is set (1) when an error is detected in slot
position 2.

3

This bit is set (1) when an error is detected in slot
position 3.

4

This bit is set (1) when an error is detected in slot
position 4.

5

This bit is set (1) when an error is detected in slot
position 5.

6

This bit is set (1) when an error is detected in slot
position 6.

7

This bit is set (1) when an error is detected in slot
position 7.

Node Address
Changed

8

This bit is set (1) when the node address switch setting
has been changed since power up.

9 thru
15

Not used - sent as zeroes.

Not Used

I/O Module Fault Bits

Node Address Changed Bit

Sl

ot

7

Sl

ot

6

Sl

ot

5

Sl

ot

4

Sl

ot

3

Sl

ot

2

Sl

ot

1

Sl

ot

0

Bit: 15 9 through 15 8 7 6 5 4 3 2 1 0