2-10 How Communication Takes Place and I/O Image Table Mapping

Memory Map of Analog Input Module Image Table - 1798-IE4

Range Selection Bits for the 1798-IE4

Decimal
Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit 17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

S

Analog Value Channel 0

Read Word 1

S

Analog Value Channel 1

Read Word 2

S

Analog Value Channel 2

Read Word 3

S

Analog Value Channel 3

Read Word 4

S

Not Used

Read Word 5

S

Not Used

Read Word 6

S

Not Used

Read Word 7

S

Not Used

Read Word 8

PU

Not Used - Set to Zero

U3

U2

U1 U0 Read Word 9

Not Used - Set to 0

C3

C2

C1

C0

Not Used - Set to 0

F3

F2

F1

F0

Write Word 1

Not Used - Set to 0

Write Word 2 thru 6

Where PU = Power up bit; U = Underrange bits for 4-20mA inputs; C = Configure select bit; F = Full range bit;
S = Sign bit (in 2’s complement)

Channel No.

Channel 0

Channel 1

Channel 2

Channel 3

F0

C0

F1

C1

F2

C2

F3

C3

Decimal Bit

00

08

01

09

02

10

03

11

0-10V dc/0-20mA

1

0

1

0

1

0

1

0

4-20mA

0

1

0

1

0

1

0

1

10 to +10V dc

1

1

1

1

1

1

1

1

Off

1

0

0

0

0

0

0

0

0

C = Configure select bit; F = Full range bit