Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual

Page 55

Advertising
background image

Publication 1798-UM001B-EN-P - November 2002

Specifications A-3

Specifications for the 1798-IB4D Module

Specifications - 1798-IB4D
Module Type

Digital Input, Sinking

Number of Channels

1 group of 4

Sensor Source Current

50 mA per connector

On-state Voltage

10-28.8V dc; 24V dc nominal

On-state Current

2-12 mA; 8 mA @ 24V dc

Off-state Voltage

5V dc maximum

Off-State Current

1.5 mA minimum

Channel Impedance

4.6K

maximum

Isolation Voltage

850V dc channel-to-system for 1s

Delay Times:Off to On
On to Off

256 us, 512 us, 1 ms, 2ms
4 ms, 8 ms, 16 ms, 32 ms
(Selectable; 256 us default)

FlexBus Current

80 mA maximum

Power Dissipation

2.0W @ 28.8V dc

Thermal Dissipation

6.8 BTU/hr. @ 28.8V dc

Indicators

4 channel status - yellow
4 diagnostic indicators- red

External DC Power
Voltage (24V dc nom.)
Current

10-28.8V dc; 5% AC ripple
300 mA maximum

Dimensions
(H x D x W)

118 mm x 57 mm x 40 mm
4.63 in. x 2.25 in. x 1.58 in.

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports
±2kV at 5kHz on signal ports

Surge Transient Immunity IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Advertising