Publication 1798-UM001B-EN-P - November 2002

Configure Your DeviceNet Adapter 3-11

The following table describes the parameters in the Advanced
Parameters
window.

Parameter #

Parameter Name

Description

3

Input Size

Number of Read words. These are determined by
other Parameter selections and cannot be set by
the user.

5

Output Size

Number of Write words. These are determined by
other Parameter selections and cannot be set by
the user.

6

Config. Size

Number of Configuration words. These are
determined by other Parameter selections and
cannot be set by the user

10

Program Mode
Behavior

Determines the state of the Outputs when the
Controller enters Program mode. The options are:

Reset to Zero

Hold Outputs in Last State

Use Safe State Output Values (Set under
Flex Config. tab.)

11

Communication
Fault Behavior

Determines the state of the Outputs when the
Controller enters Program mode. The options are:

Reset to Zero

Hold Outputs in Last State

Use Safe State Output Values (Set under
FLEX Config. tab.)

13

Module Fault

Determines the state of the Inputs in the event of a
Module Fault. The options are:

Zero Inputs

Hold Last Input Values