Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual

Page 62

Advertising
background image

Publication 1798-UM001B-EN-P - November 2002

A-10 Specifications

Specifications - 1798-OE2 Analog Output Module
Thermal Dissipation

8.5 BTU/hr @ 28.8V dc

Indicator

1 fault LED Indicator - red

External DC Power
Voltage (24V dc nom.)
Current

10-28.8V dc; 5% AC ripple
85 mA @ 24V dc

Dimensions
(H x D x W)

118 mm x 57 mm x 40 mm
4.63 in. x 2.25 in. x 1.58 in.

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry
Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
–40 to 85°C (–40 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports
±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Conductors

See publication DN-6.7.2

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Enclosure

Meets IP67