Rockwell Automation 1798-IB4 FlexArmor User Manual User Manual

Page 26

Advertising
background image

Publication 1798-UM001B-EN-P - November 2002

2-12 How Communication Takes Place and I/O Image Table Mapping

Description of 1798-OE2 Image Table Mapping

Memory Map of Analog Output Module Image Table - 1798-OE2

I/O Image

Input Size

0 to 1 Words

PU

Not Used

Diagnostics

Analog Output Data 0

Output Size

Analog Output Data 1

1 to 6 Words

Not Used

Not Used

Not Used

OE

Not Used Config. Select Not Used Full Range

Not Used

Not Used

Not Used

Not Used

Not Used

Decimal
Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit 17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

PU

Not Used - Set to Zero

W1

W0

Read Word 1

S

Analog Value Channel 0

Write Word 1

S

Analog Value Channel 1

Write Word 2

S

Not Used

Write Word 3

S

Not Used

Write Word 4

S

Not Used - Set to 0

OE1 OE0 Write Word 5

S

Not Used - Set to 0

C1

C0

Not Used - Set to 0

F1

F0

Write Word 6

S

Not Used - Set to 0

Write Word 7 thru 14

Where PU = Power up bit; W = Diagnostic bits for current output broken or load resistance high (Not used on voltage
outputs.); OE = Output enable bits (bit 00 corresponds to output 0, bit 01 corresponds to output 1. ATTENTION: These bits
must be set to 1
. C = Configure select bit; F = Full range bit; S = Sign bit (in 2’s complement)

Advertising