A-6 Specifications

Specifications - 1798-IE4 Analog Input Module (Continued)
Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports
±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on
power ports
±1kV line-line(DM) and ±2kV line-earth(CM) on signal
ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 80MHz

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Enclosure

Meets IP67

Certifications
(When product is marked)

c-UL-us UL Listed Industrial Control Equipment,

certified for US and Canada

UL

UL Listed Industrial Control Equipment

CE

1

European Union 89/336/EEC EMC Directive,

compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial

Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

1

Australian Radiocommunications Act,

compliant with: AS/NZS 2064; Industrial

Emissions

1.

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.