3.0 INSTALLATION

This section describes how to install and remove the module and its

cable assembly.

3.1

Wiring

The installation ofwiring should conform to all applicable codes.
To reduce the possibility ofelectrical noise interfering with the proper

operation ofthe control system, exercise care when installing the

wiring from the system to the external devices. For detailed

recommendations refer to IEEE 518.

3.2

Initial Installation

Use the following procedure to install the module:
Step 1.

Turn off power to the system. All power to the rack as well

as all power to the wiring leading to the module should be

off.

Step 2.

Mount the terminal strips (M/N 57C375) on a panel. The

terminal strips should be mounted to permit easy access

to the screw terminals on the terminal strips. Make certain

that the terminal strips are close enough to the rack so that

the cable will reach between the terminal strips and the

module.

Step 3.

Fasten field wires to the terminal strips. Typical field

connections are shown in figures 3.1, 3.2, and 3.3.
Refer to Appendix C for the arrangement of terminal board

connections. Make certain that all field wires are securely

fastened.

A1

A2

+

-

Figure 3.1 Ć Typical Field Connections for Contact Closures