2 bus error – Rockwell Automation 57C419 5V-24V DC Input Module User Manual

Page 27

Advertising
background image

5Ć3

5.2

Bus Error

Problem: A 31" or 51" through 58" appears on the Processor

module's LED. This error message indicates that there was a bus

error when the system attempted to access the module. The possible

causes of this error are a missing module, a module in the wrong

slot, or a malfunctioning module. It is also possible that the user is

attempting to write to the wrong registers on the module. Use the

following procedure to isolate a bus error:
Step 1.

Verify that the input module is in the correct slot and that

the I/Odefinitions are correct.
Refer to figure 3.4. Verify that the slot number being

referenced agrees with the slot number defined in the

configuration task. Verify that the register number and bit

number are correct.
For remote I/Oinstallations, also verify that the master slot

and drop number are defined correctly.

Step 2.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR to monitor

the four registers on the input module. If the I/O MONITOR

is able to monitor the inputs, the problem lies in the

application software (proceed to step 3). If the I/Omonitor

cannot monitor the inputs, the problem lies in the

hardware (proceed to step 4).

Step 3.

Verify that the user application program is correct.
Registers 0 and 1 of the input module cannot be written to.

If a BASIC task caused the bus error, the error log will

contain the statement number in the task where the error

occurred. If a Ladder Logic or Control Block task caused

the error, you will need to search the task for any instances

where you used an input as a ladder logic coil or wrote to

it in a Control Block task.

Step 4.

Verify that the hardware is working correctly.
Verify the hardware functionality by systematically

swapping out the input module, the Processor module(s)

and the backplane. After each swap, if the problem is not

corrected, replace the original item before swapping out

the next item.
To test the remote rack, connect a dumb terminal or a

personal computer running terminal emulation software

such as Kermit to the slave remote I/Omodule RSĆ232C

port. Set the port parameters on the terminal or computer

to 8 bits, 1 stop bit, no parity and a baud rate of 1200.

Connect the remote I/Omodule (C<CR> with Kermit).

See the Remote I/Oinstruction manual JĆ3606 for how to

test the module.
If you cannot determine the problem, replace the input

module. Next, replace the slave remote I/Omodule. If the

problem persists, take all of the modules out of the remote

backplane except the slave remote I/Omodule and the

input module. If the problem is now corrected, one of the

other modules in the rack is malfunctioning. Reconnect

the other modules one at a time until the problem

Advertising