Step 3.

Verify that the input circuit on the module is working

correctly.
Toggle the input device. Verify that the LED associated

with the particular bit is also toggling. If it is not, the input

circuit on the module is malfunctioning.

Step 4.

Verify that the module can be accessed.
Connect the programmer to the system and run the

ReSource Software. Use the I/O MONITOR function to

display register 1 and 2. Toggle the input device to

determine whether the bit is changing state. If it is not, the

input circuit on the module is malfunctioning.

Step 5.

Verify that the hardware is working correctly.
Systematically swap out the input module, the processor

module(s), and the backplane. After each swap, if the

problem has not been corrected, replace the original item

before swapping out the next item.

5.3.2

Hardware Event TimeĆOut

Problem: All tasks in the chassis are stopped and error code 12"

appears on the faceplate of the Processor module. The interrupt has

either never occurred or is occurring at a slower frequency than the

value specified in the timeout" parameter in the event definition. Use

the following procedure to isolate the problem:
Step 1.

Verify that the timeout value is set correctly.
Check the value specified, if any, in the timeout"

parameter in the event definition. The unit is ticks. Each

tick is equal to 5.5 msec. The timeout value should be at

least 2 ticks greater than the interrupt frequency. It can

reasonably range up to 1.5 times the interrupt frequency.

Note that the `timeout' parameter is usually disabled since

the interrupt doesn't usually happen on a timed basis.

Step 2.

Check for no interrupt.
Refer to section 5.3.1.

5.3.3

Hardware Event Count Limit Exceeded

Problem: All tasks in the chassis are stopped and error code 1B"

appears on the faceplate of the Processor module. A hardware

interrupt has occurred but no task is waiting. Use the following

procedure to isolate the problem:
Step 1.

Verify that the user application program is correct.
Verify that your interrupt response task contains either a

WAIT ON event" or CALL SCAN LOOP" statement that

will be executed. Check carefully to determine whether a

higher priority task is preventing the interrupt response

task from running.
Make sure that the ordering of your statements agrees

with the examples in section 4.4.

Step 2.

Verify that the signal from the external device is clean.
Connect a scope to the input terminals and monitor the

pulse waveform from the external device. The waveform