3 interrupt problems – Rockwell Automation 57C419 5V-24V DC Input Module User Manual

Page 28

Advertising
background image

5Ć4

reappears. If the problem proves to be neither in the

remote I/O system nor in the remote rack, try replacing the

backplane.

5.3

Interrupt Problems

Problem: No interrupts at all, or too many (unexpected) interrupts,

signified by error codes being displayed on the faceplate of the

Processor module. Go through the following steps first before going

on the the more specific troubleshooting steps:
Step 1.

Verify that the input module is in the correct slot.
Refer to figure 3.4.

Step 2.

Verify that the I/O definitions are correct.
Verfiy that the configuration task contains the proper

interrupt control definitions. Refer to the example in

section 4.6.

Step 3.

Verify that the user application program is correct.
Verify that the application program that uses the symbolic

names defined in the configuration task has defined those

names as COMMON.
Compare your interrupt task with the examples given in

sections 4.4.1 and 4.4.2. Make sure that the actions shown

in the examples are performed in the same order in your

task.

5.3.1

No Interrupts

Problem: The task does not execute but no error codes are displayed

on the Processor module faceplate. If interrupts are never received

and the timeout" parameter in the event definition was disabled, the

task will never execute. Use the following procedure to isolate the

problem:
Step 1.

Verify that the user application program is correct.
Verify that your interrupt response task is checking the

proper latch status bit to determine which bit caused the

interrupt. Confirm that when an interrupt has been located,

the latch reset bit is being reset.
Compare your interrupt task with the examples given in

sections 4.4.1 and 4.4.2. Make sure that the actions shown

in the examples are performed in the same order in your

task.

Step 2.

Verify that the input is wired to the correct device.
Confirm that all connections at the terminal strip are tight.

Connect a voltmeter to the proper points on the terminal

strip and toggle the device. The voltĆ meter should

alternate between 0 and the DĆC power supply voltage

(5Ć24 volts). If this does not happen, there is a problem

with either the external device, the DĆC power supply, or

the wiring to the terminal strip.
If the device generates a pulse output, use a scope and

verify that the pulse width is at least .7 msec.

Advertising