0 diagnostics and troubleshooting, 1 incorrect data – Rockwell Automation 57C419 5V-24V DC Input Module User Manual

Page 25

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections.

5.1

Incorrect Data

Problem: The data is either always off, always on, or different than

expected. The possible causes of this are a module in the wrong slot,

a programming error, or a malfunctioning module. It is also possible

that the input is either not wired or wired to the wrong device. Use the

following procedure to isolate the problem:
Step 1.

Verify that the input module is in the correct slot and that

the I/O definitions are correct.
Refer to figure 3.4. Verify that the slot number being

referenced agrees with the slot number defined in the

configuration. Verify that the register number and bit

number are correct.
For remote I/O installations, also verify that the master slot

and drop number are defined correctly.

Step 2.

Verify that the input is wired to the correct device.
Confirm that all connections at the terminal strip are tight.

Connect a voltmeter to the proper points on the terminal

strip and toggle the device. The voltmeter should alternate

between 0 and the DĆC power supply voltage (5Ć24 volts).

If this does not happen, there is a problem with either the

external device, the DĆC power supply, or the wiring to the

terminal strip.
Check the cable for continuity between the faceplate

connector and the terminal strip.

Step 3.

Verify that the input circuit on the module is working

correctly.
Toggle the input device. Verify that the LED associated

with the particular bit is also toggling. If it is not, the input

module is malfunctioning.

Step 4.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR function.

Toggle the input device to determine whether the bit is

changing state.
If the I/O MONITOR is able to read the input, the problem

lies in the application software (proceed to step 5). If the

I/O MONITOR cannot read the inputs, the problem lies in

the hardware (proceed to step 6).

Step 5.

Verify that the user application program is correct.
Verify that the application program that references the

symbolicnames assigned to the module has declared

those names COMMON in application tasks.
Verify that the symbolicname in question is being

referenced in the application program. This can be done

Advertising