Rockwell Automation 57C419 5V-24V DC Input Module User Manual

Page 26

Advertising
background image

5Ć2

indirectly by monitoring the name with the VARIABLE

MONITOR function in the ReSource Software.
If operation is intermittent, verify that the task reading the

module is executing fast enough to catch all of the input

changes.

Step 6.

Verify that the hardware is working correctly.
Verify the hardware functionality by systematically

swapping out modules. After each swap, if the problem is

not corrected, replace the original module before

swapping out the next module.
D To test local I/O, first replace the input module. Next,

replace the Processor module (s). If the problem

persists, take all of the modules except one Processor

module and the input module out of the backplane. If

the problem is now corrected, one of the other

modules in the rack is malfunctioning. Replace the

other modules one at a time until the problem

reappears. If none of these tests reveals the problem,

replace the backplane.

D To test remote I/O, first verify that the remote I/O

system is communicating with the drop that contains

the input module being tested. Next, determine

whether the input module is the only module that is not

working. If more than one module is not working

correctly, the problem most likely lies in the remote I/O

system. If the problem does not lie in the system, it

probably involves the remote rack.

D To test the remote rack, connect a dumb terminal or a

personal computer running terminal emulation

software such as Kermit to the slave remote I/O module

RSĆ232C port. Set the port parameters on the terminal

or computer to 8 bits, 1 stop bit, no parity and a baud

rate of 1200. Connect the remote I/O module (C<CR>

with Kermit). See the Remote I/O instruction manual

(JĆ3606) for how to test the module.
If you cannot determine the problem, replace the input

module. Next, replace the slave remote I/O module. If

the problem persists, take all of the modules out of the

remote backplane except the slave remote I/O module

and the input module. If the problem is now corrected,

one of the other modules in the rack is malfunctioning.

Reconnect the other modules one at a time until the

problem reappears. If the problem proves to be neither

in the remote I/O system nor in the remote rack, try

replacing the backplane.

Advertising