Controller template overview – Rockwell Automation System Release 3.0 PlantPAx System Application Templates Quick Start User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication PROCES-QS001A-EN-P - October 2013

Chapter 1 Configure the Controller Application

Controller Template Overview

Controller templates provide the necessary task configurations that are required for the PlantPAx system. Controller
template options also are provided with pre-loaded PlantPAx Library content if the PlantPAx Library is to be used. Library
content definitions use controller memory, so use the guidance in

Table 2

when selecting the appropriate template for your

application.

For each controller, you must choose one of three templates to begin system configuration.

Table 2

and

Table 3

show the

templates that are recommended (denoted by ‘X’) based on the selected controller.

IMPORTANT

Controller templates are distributed with the PlantPAx Library of Process Objects. To download the templates, see Knowledgebase
Answer ID 62682 at

https://www.rockwellautomation.custhelp.com

.

Table 2 - PlantPAx Controller Templates and ControlLogix Controllers

Simplex Controllers

Redundant Controllers

1756-L71

1756-L72

1756-L73

1756-L74

1756-L75

1756-L73

1756-L74

1756-L75

User memory

2 MB

4 MB

8 MB

16 MB

32 MB

8 MB

16 MB

32 MB

No library

X

X

X

X

X

X

X

X

Basic library

(1)

(1) Basic library template is approximately 0.4 MB.

X

X

X

X

X

X

X

X

All library

(2)

(2) All library template is approximately 1.2 MB.

X

X

X

X

X

X

Table 3 - PlantPAx Controller Templates and CompactLogix Controllers

1769-L24ER-QBFC1B

1769-L33ER

User memory

0.75 MB

2 MB

No library

X

X

Basic library

(1)

(1) Basic library template is approximately 0.4 MB.

X

X

All library

(2)

(2) All library template is approximately 1.2 MB.

Table 4 - Controller Template Descriptions

Template

Name

(1)

(1) PlantPAx Library 3.0 supports RSLogix 5000 software version 18 and later. Templates are provided with software version 18 so they can be used in any later supported version of RSLogix 5000.

Description

No library

RSL5k_18_Template_PlantPAx_noLib.acd

No PlantPAx Library of Process Objects.

Basic library

RSL5k_v18_Template_PlantPAxLib_3_0_00_basic.acd

(2)

(2) The service release number (boldfaced) can change as service revisions are created.

PlantPAx Library of Process Objects, includes diagnostics and the following Process Add-On
Instructions: P_AIn, P_Alarm, P_AOut, P_DIn, P_Gate, P_DOut, P_Intlk, P_Mode, P_Motor,
P_Perm, P_Reset, P_ValveSO, P_VSD, P_PIDE, T_ADD, T_Clock, T_DST, T_Valid.

All library

RSL5k_18_Template_PlantPAxLib_3_0_00_all.acd

Complete PlantPAx Library of Process Objects.

Advertising