Rockwell Automation Publication PROCES-QS001A-EN-P - October 2013

37

Create Your HMI Project Chapter 2

7. Click the Priorities and History tab.

8. Check the Enable history checkbox to enable alarm and event history.

9. From the Database definition pull-down menu, choose the alarm history database that was created during the

installation of the FactoryTalk View SE software.

10. Click Apply, and OK.

11. Repeat

step 1

through

step 10

for each alarm server in your application.

IMPORTANT

The alarm history database requires a separate SQL server installation. If there is no database selection available under
Alarm and Event History, a database must be created. Refer to the FactoryTalk Alarms and Events System Configuration
Guide, publication

FTAE-RM001

.

IMPORTANT

We recommend that alarm server redundancy be configured at the end of the project after the majority of your HMI
application is developed.