Create Your HMI Project Chapter 2
7. Click the Priorities and History tab.
8. Check the Enable history checkbox to enable alarm and event history.
9. From the Database definition pull-down menu, choose the alarm history database that was created during the
installation of the FactoryTalk View SE software.
10. Click Apply, and OK.
11. Repeat
through
for each alarm server in your application.
IMPORTANT
The alarm history database requires a separate SQL server installation. If there is no database selection available under
Alarm and Event History, a database must be created. Refer to the FactoryTalk Alarms and Events System Configuration
Guide, publication
.
IMPORTANT
We recommend that alarm server redundancy be configured at the end of the project after the majority of your HMI
application is developed.