Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual

Page 15

Advertising
background image

Publication GMSI10-UM001C-EN-E - June 2011

Installing the XM-720 Machine Monitor 15

Table 2.2 Terminal Block Assignments

1

It is assumed that the relay is to be configured as failsafe.

2.

It is assumed that the relay is to be configure as non-failsafe.

Terminal
Block

No.

Name

Description

TB1
(top)

E

AC Earth Ground

AC equipment earth ground

L

AC Input Line

AC power (hot)

N

AC Input Neutral

AC common (neutral)

4

Fault Relay NC

1

Normally Closed contact for Module/Transducer Fault relay

5

Fault Relay Common

Common for Module/Transducer Fault relay

6

Fault Relay NO

1

Normally Open contact for Module/Transducer Fault relay

7

Warning Relay NO

2

Normally Open contact for Warning relay

8

Warning Relay Common

Common for Warning relay

9

Warning Relay NC

2

Normally Closed contact for Warning relay

10

Trip Relay NO

2

Normally Open contact for Trip relay

11

Trip Relay Common

Common for Trip relay

12

Trip Relay NC

2

Normally Closed contact for Trip relay

13

Reset Relay Switch

Switch input to reset internal relays

14

Switch RTN

Switch return for Reset Relay and Setpoint Multiplier switch

15

Setpoint Multiplier Switch

Switch input to activate Setpoint Multiplication (active open)

16

24V Common

Tachometer 24V power return

TB2
(bottom)

17

Xducer 1 (+)

Vibration transducer channel 1 connection

18

Xducer 1 (-)

Vibration transducer channel 1 connection

19

Chassis GND

Connection to chassis ground (channel 1 shield)

20

Xducer 2 (+)

Vibration transducer channel 2 connection

21

Xducer 2 (-)

Vibration transducer channel 2 connection

22

Chassis GND

Connection to chassis ground (channel 2 shield)

23

Xducer +24V

Transducer power, positive side; used to power external sensor

24

Xducer -24V

Transducer power, negative side; used to power external sensor

25

4-20mA 1 (+)

3

4-20mA output; channel 1
250 ohm maximum load

26

4-20mA 1 (-)

3

27

Chassis GND

Connection to chassis ground (4-20mA outputs shield)

28

4-20mA 2 (+)

3

4-20mA output; channel 2
250 ohm maximum load

29

4-20mA 2 (-)

3

30

Tachometer In (+)

Tachometer transducer/signal input, positive side

31

Tachometer In (-)

Tachometer transducer/signal input, negative side

32

Chassis GND

Connection to chassis ground (tachometer shield)