Publication GMSI10-UM001C-EN-E - June 2011

Configuring the XM-720 49

To modify the relay parameters, follow these steps.

1. In the Configuration Tool, click the Alarm, Relay, and 4-20 mA tab.

You will see a screen similar to this.

2. Select the relay Number that you want to modify or configure.

3. Enter or select the desired parameters to set up the behavior of the relay.

This includes:

• the number of seconds after an alarm condition has been exceeded

before the relay activates (activation delay)

• the activation logic and the alarm(s) that the relay monitors
• the conditions that will cause the relay to activate (for example,

module fault, measurement exceeds danger level thresholds)

• whether the relay is latched and failsafe

4. When you are finished, choose Device > Download to Device to

download your changes to the XM module.

Check the checkbox if the relay must be explicitly

reset. Uncheck the checkbox if the relay is to

reset itself once the alarm condition has passed.

The alarm conditions that cause the relay to

activate. More than one can be checked.

The relay activation logic and what

alarm(s) the relay is to monitor.

Check the checkbox if the relay is normally

energized. Uncheck the checkbox if the relay is

normally de-energized.

The activation logic must persist for this length of

time before the relay is activated.

TIP

Refer to Chapter 3 in the XM Module User Guide
for a detailed description of the configuration
parameters.

TIP

Press F1 to display the online help topic for the
current tab or dialog.