Connecting a powered sensor – Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual

Page 26

Advertising
background image

Publication GMSI10-UM001C-EN-E - June 2011

26 Installing the XM-720 Machine Monitor

Figure 2.12 Velocity Sensor Wirings

Connecting a Powered Sensor

The figure below shows the wiring of a powered sensor, such as Entek IRD
Model 544 or 580 Vibration Pickup, to the XM-720 back panel.

TYPICAL WIRING FOR COIL-BASED VELOCITY SENSOR

TO XM-720 BACK PANEL

Shield

Channel 1 Input Signal

Signal Common

Shield

Channel 2 Input Signal

17

18
19

20
21

22

Signal Common

Pin A - Si gnal
Pin B - Common

Cable shield not
connected at this end

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

IMPORTANT

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield to one of the Chassis
GND terminals on the XM-720 terminal block and not at
the transducer. Any of the Chassis GND terminals on the
XM-720 terminal block provides a grounding point for the
cable shield.

IMPORTANT

Using the XM Serial Configuration Utility, make certain the
IEPE Power parameter is disabled. Refer to Transducer
Parameters on page 44.

Advertising
This manual is related to the following products: