Rockwell Automation 1440-PK02-05M2 XM-720 Machine Monitor User Manual

Page 33

Advertising
background image

Publication GMSI10-UM001C-EN-E - June 2011

Installing the XM-720 Machine Monitor 33

To determine the signal amplitude on bargraph meter

To determine the signal amplitude in engineering units, use the following
formula:

To determine placement for Alert and Danger Threshold Arrows

The caption sheet (included in package) contains red (danger) and orange
(alert) arrows for you to place on the meter to show the alert and danger
threshold levels. Use the following formula to determine placement of the
arrows.

Amplitude

Bargraph % 100

(

)

4-20mA Max Range value 4-20mA Min Range value

(

) 4-20mA Min Range value

+

×

=

EXAMPLE

meter reading: 40%
4-20mA Min Range value: 0 mils
4-20mA Max Range value: 5 mils

amplitude = (40% / 100) x (5 -0) + 0 = 2 mils

EXAMPLE

Alert Threshold value in configuration: 2.5 g
4-20mA Min Range value in configuration: 0 g
4-20mA Max Range value in configuration: 5 g

Alert threshold % sticker = (2.5 - 0) x 100% / (5 - 0) = 50%

EXAMPLE

Danger threshold value in configuration: 3.5 g
4-20mA Min Range value in configuration: 0 g
4-20mA Max Range value in configuration: 5 g

Danger threshold % sticker = (3.5 - 0) x 100% / (5 - 0) =

70%

Threshold %

Threshold value 4-20mA Min Range value

(

) 100%

×

4-20mA Max Range value 4-20mA Min Range value

(

)

----------------------------------------------------------------------------------------------------------------------------------------------

=

Place the orange
arrow sticker on meter
to show alert
threshold level (e.g.
50%).

Place the red arrow
sticker on meter to
show danger threshold
level (e.g. 70%).