42 Configuring the XM-720

3. Connect the computer’s serial port to the XM-120/121/122 module’s

mini-connector using the special serial cable that is shipped with the
XM-720 monitor. The mini-connector is accessed from the top or side
of the XM-720 enclsure.

4. Power up the XM-720 module if you haven’t already done so, and start

the XM Serial Configuration Utility program. Click the Start program,
and then choose Programs > Entek > XM > Serial Config Utility.

5. Click the Configure button on the XM Serial Configuration Utility

screen. The Configuration Tool for the connected XM module appears.

WARNING

If you connect or disconnect the serial cable with power
applied to the module or the serial device on the other end
of the cable, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.

TIP

The Configuration Utility defaults to the COM 1
serial port. If you are not using COM 1, select the
correct COM port on the XM Serial Configuration
Utility screen.

When you are connected to an XM module, the XM
Serial Configuration Utility automatically detects the
type of module. The module type appears on the
XM icon, and the connection icon changes to show
the connection.

Cable connects to the

mini-connector on top

of the

XM-120/121/122

module.