Serial Converter Parameters

B-1

A

PPENDIX

B

Serial Converter Parameters

Selects the module’s mode of operation. Leave at 0 = Auto setting
when used with software tools. Note that options 3 = RTU Master
and 4 = RTU Passthru are reserved for future use.

Important:

Adapter Cfg (01) must be set to Auto (default) for
VS Utilities to operate. HyperTerminal can be used if
Adapter Cfg (01) needs to be changed.

Selects the DF1 node address for the Serial Converter. This is a
decimal value.

01

Adapter Cfg

Range:

0 = Auto
1 = Master
2 = Slave
3 = RTU Master
4 = RTU Passthru

Default:

0 = Auto

Type:

Read/Write

Reset Required: Yes

02

DF1 Addr Cfg

Range:

0 to 254

Default:

1

Type:

Read/Write

Reset Required: Yes