Rockwell Automation MD60 Serial Converter Module - M/N MDCOMM 232 User Manual
Page 40

B-4
Serial Converter Module (MDCOMM-232)
Number of DF1 packets received by the Serial Converter. The value
of this parameter is normally approximately equal to the value of
DF1 Packets Sent (07).
Number of DF1 messages that were sent but not acknowledged.
This value is normally a low value. If it is continually incrementing
and you are having communications problems, use a lower baud
rate or replace the RECBL-SFC serial cable.
Number of ENQ (Enquiry) characters sent by the Serial Converter.
This value is normally a low value. If it is continually incrementing
and you are having communications problems, use a lower baud
rate or replace the RECBL-SFC serial cable.
Number of ENQ (Enquiry) characters received by the Serial
Converter.
This value is normally a low value. If it is continually incrementing
and you are having communications problems, use a lower baud
rate or replace the RECBL-SFC serial cable.
08
DF1 Packets Rcvd
Range:
0 to 4294967295
Default:
0
Type:
Read Only
09
Undelivered Msgs
Range:
0 to 65535
Default:
0
Type:
Read Only
10
ENQs Sent
Range:
0 to 65535
Default:
0
Type:
Read Only
11
ENQs Received
Range:
0 to 65535
Default:
0
Type:
Read Only