6 input line fuse selection, E 3.1. b – Rockwell Automation SA3100 AC Power Modules User Manual

Page 28

Advertising
background image

3-10

SA3100 Power Modules

.

Table 3.1 – Maximum Recommended Input Line Fuse Ratings

Drive Catalog No.

kW (HP)

Rating

200 - 240V

Rating

380 - 480V

Rating

500 - 600V

Rating

UL Class CC, T, J

1

- BS88 (non-UL installations)

1. Both fast acting and slow blow fuses are acceptable.

SA3100-_001-_ _

0.75 (1)

10A

6A

6A

SA3100-_003-_ _

2.2 (3)

15A

10A

10A

SA3100-_007-_ _

5.5 (7.5)

40A

20A

15A

SA3100-_010-_ _

7.5 (10)

50A

30A

20A

SA3100-_015-_ _

11 (15)

70A

35A

25A

SA3100-_020 -_ _

15 (20)

100A

45A

35A

SA3100-_025 -_ _

18.5 (25)

100A

60A

40A

SA3100-_030 -_ _

22 (30)

125A

70A

50A

SA3100-_040 -_ _

30 (40)

150A

80A

60A

SA3100-_050 -_ _

37 (50)

200A

100A

80A

SA3100-_060 -_ _

45 (60)

250A

125A

90A

SA3100-_075 -_ _

56 (75)

-

150A

110A

SA3100-_100 -_ _

75 (100)

-

200A

150A

SA3100-_125 -_ _

93 (125)

-

250A

175A

SA3100-_150 -_ _

112 (150)

-

300A

225A

SA3100-_200 -_ _

149 (200)

-

400A

350A

SA3100-_250 -_ _

187 (250)

-

450A

400A

Bussmann FWP/Gould Shawmut A-70C Semi-conductor Type

SA3100-_300 -_ _

224 (300)

-

450A

400A

SA3100-_350 -_ _

261 (350)

-

500A

450A

SA3100-_400 -_ _

298 (400)

-

600A

500A

SA3100-_450 -_ _

336 (450)

-

800A

600A

SA3100-_500 -_ _

373 (500)

-

800A

800A

SA3100-_600 -_ _

448 (600)

-

900A

800A

SA3100-_650 -_ _

485 (650)

-

-

800A

SA3100-_800 -_ _

597 (800)

-

700A

2

700A

2

2. Two fuses in parallel are required.

Advertising