6 input line fuse selection, E 3.1. b – Rockwell Automation SA3100 AC Power Modules User Manual
Page 28

3-10
SA3100 Power Modules
.
Table 3.1 – Maximum Recommended Input Line Fuse Ratings
Drive Catalog No.
kW (HP)
Rating
200 - 240V
Rating
380 - 480V
Rating
500 - 600V
Rating
UL Class CC, T, J
1
- BS88 (non-UL installations)
1. Both fast acting and slow blow fuses are acceptable.
SA3100-_001-_ _
0.75 (1)
10A
6A
6A
SA3100-_003-_ _
2.2 (3)
15A
10A
10A
SA3100-_007-_ _
5.5 (7.5)
40A
20A
15A
SA3100-_010-_ _
7.5 (10)
50A
30A
20A
SA3100-_015-_ _
11 (15)
70A
35A
25A
SA3100-_020 -_ _
15 (20)
100A
45A
35A
SA3100-_025 -_ _
18.5 (25)
100A
60A
40A
SA3100-_030 -_ _
22 (30)
125A
70A
50A
SA3100-_040 -_ _
30 (40)
150A
80A
60A
SA3100-_050 -_ _
37 (50)
200A
100A
80A
SA3100-_060 -_ _
45 (60)
250A
125A
90A
SA3100-_075 -_ _
56 (75)
-
150A
110A
SA3100-_100 -_ _
75 (100)
-
200A
150A
SA3100-_125 -_ _
93 (125)
-
250A
175A
SA3100-_150 -_ _
112 (150)
-
300A
225A
SA3100-_200 -_ _
149 (200)
-
400A
350A
SA3100-_250 -_ _
187 (250)
-
450A
400A
Bussmann FWP/Gould Shawmut A-70C Semi-conductor Type
SA3100-_300 -_ _
224 (300)
-
450A
400A
SA3100-_350 -_ _
261 (350)
-
500A
450A
SA3100-_400 -_ _
298 (400)
-
600A
500A
SA3100-_450 -_ _
336 (450)
-
800A
600A
SA3100-_500 -_ _
373 (500)
-
800A
800A
SA3100-_600 -_ _
448 (600)
-
900A
800A
SA3100-_650 -_ _
485 (650)
-
-
800A
SA3100-_800 -_ _
597 (800)
-
700A
700A
2
2. Two fuses in parallel are required.