Technical Specifications

A-3

Overload Capability

Continuous: 100% Fundamental current

1 minute: 150% (B - G frame Power Modules)
135% (H frame Power Modules)

Output Frequency Range

Vector Mode: 0 - 400 Hz (limited by feedback devices)

V/Hz Mode: 0 - 600 Hz

Output Waveform

Sinusoidal (PWM)

Maximum Short Circuit Current Rating

200,000 A rms symmetrical, 600 volts (when used with AC input line fuses
specified in table 3.2).

Ride Through

2 seconds minimum

Efficiency

97.5% at rated amps, nominal line volts

Ground Fault Trip Threshold

Power Module

Model Numbers

Trip Level

A001 - A003

Q 001 - Q 003

B 001 - B 003

R 001 - R 003
C 001 - C 003

W 001 - W 003

20A

A 007 - A 125

Q 007 - Q 125

B 007 - B 600

R 007 - R 800
C 007 - C 650

W 007 - W 800

100A