A-6

SA3100 Power Modules

Enclosure Requirements

Table A.2 – Enclosure Requirements

Power

Module

Model No.

Base

Derate

Amps

1

Derating

Curve

2,3

Heat

Dissipation

Watts

2,3

Heatsink

Watts

2

Total

Watts

2

230 VAC Output Drives

A/Q 001

4.5

None

17

32

49

A/Q 003

12

None

33

72

105

A/Q 007

27

None

156

486

642

A/Q 010

34

Fig A.1

200

721

921

A/Q 015

48

Fig A.2

205

819

1024

A/Q 020

65

Fig A.3

210

933

1143

A/Q 025

78

Fig A.4

215

1110

1325

A/Q 030

80

4

220

1110

1330

A/Q 040

120

Fig A.5

361

1708

2069

A/Q 050

149

Fig A.6

426

1944

2370

A/Q 060

180

Fig A.7

522

2664

3186

A/Q 075

240

Fig A.8

606

2769

3375

A/Q 100

291

Fig A.9

755

3700

4455

A/Q 125

327

4

460 VAC Output Drives

B/R 001

2.5

None

15

20

35

B/R 003

6

None

23

54

77

B/R 007

14

None

91

270

361

B/R 010

21

None

103

394

497

B/R 015

27

Fig A.10

117

486

603

B/R 020

34

Fig A.1

140

628

768

B/R 025

42

Fig A.11

141

720

861

B/R 030

48

Fig A.2

141

820

961

B/R 040

65

Fig A.3

175

933

1108

B/R 050

78

Fig A.4

193

1110

1303

B/R 060

97

4

361

1708

2069

B/R 075

120

Fig A.12

361

1708

2069

B/R 100

150

Fig A.13

426

1944

2370

B/R 125

180

Fig A.14

522

2664

3186

B/R 150

240

Fig A.8

606

2769

3375

B/R 200

291

Fig A.9

755

3700

4455

B/R 250

327

Fig A.15

902

4100

5002

B/R 300

406

4

1005

4805

5810

B/R 350

459

4

1055

5455

6510

B/R 400

505

4

1295

6175

7470

B/R 450

570

4

1335

6875

8210

B/R 500

599

Fig A.16

1395

7800

9200

B/R 600

673

Fig A.17

1485

8767

10252

R 800

900

4

N/A

N/A

N/A