2-6
SA500 Diagnostics, Troubleshooting, and Start-Up Guidelines
2.4.3 How to Clear the Drive Fault and Drive Warning Registers
After a drive fault has been detected, the programmer must do the following before the
drive can be restarted:
Step 1. Reset the command bit that is currently set in the Drive Control register
(100/1100).
Step 2. Correct the fault.
Step 3. Set and reset the Fault Reset bit (register 100/1100, bit 8, FLT_RST@) to
clear the Drive Fault register (200/1200). (Note that the Fault Reset bit is
edge sensitive.)
Step 4. Set the desired command bit in the Drive Control register (100/1100).
After a drive warning has been detected, the programmer can clear the entire Drive
Warning register by setting and resetting the Warning Reset bit (register 100/1100,
bit 9, WRN_RST@). (Note that the Warning Reset bit is edge sensitive.)