Specifications – Rockwell Automation 440R MSR241 Minotaur Safety Relay User Manual
Page 13
![background image](/manuals/581372/13/background.png)
MSR241 DeviceNet for Safety System MSR200
13
______________________________________________________________
Specifications
Output specification K1, K2
Nominal switching capacity (resistive
load)
2A 30V DC
Max. switching power (resistive load)
60W
Max. switching voltage
220V DC
Max. switching current
2A
Min. switching capacity
10µA 10mV DC
UL/CSA rating
2A 30V DC
0.3A 110V DC
0.5A 125V DC
General Specifications
Indicators
Module Status red/green
Network Status red/green
Output Status K1, K2 green
Communication rate
125 kBaud, 250kBaud, 500 kBaud
Max. length of fieldbus segment
100m … 500m (depends on baud rate /
on the cable)
Isolation
Output to DeviceNet
Output to Output
500V ac/60s
500V ac/60s
DeviceNet Power
Voltage
Current
11 – 25V dc
170mA maximum
Temperature
-5°C – 50°C
Drg No:
57602
/ Issue No: 0 Feb. 04