Connect the MSR241 with the safety system MSR200 via
ribbon cable


The MSR241 mount to a panel or DIN rail, which must be grounded before
installing the module.

Connect the MSR241 either to the Basic module or to an output extension
module on the right side of the MSR200 safety system via ribbon cable.
The terminator for the EDM loop is integrated in the MSR241.

Connect the relay outputs


If you want to use the relay outputs of the MSR241 connect them to your
application.

Connect the DeviceNet Cable


Refer to following information when connecting the DeviceNet wire to the
MSR241.

1. Connect the DeviceNet cable (drop line) to the unsealed DeviceNet

terminal connector.

2. Connect the terminal connector to the module. Use the side screws on

the terminal connector to fasten it to the module.


IMPORTANT

Pin Number

Wire Color

Abbreviation

Description

1

Black V-

Power

return

2

Blue

CAN_L

Data line (CAN Low)

3

Clear

Shield

Between cable jacket and wire

4

White

CAN_H

Data line (CAN High)

5

Red

V+

Positive voltage (hot)


The bus cable must be terminated with a resistor (121

Ω / +/- 1% / 0,25W).

The resistor is contacted with CAN_H and CAN_L.