Byte definitions – Rockwell Automation 440R MSR241 Minotaur Safety Relay User Manual

Page 4

Advertising
background image

MSR241 DeviceNet for Safety System MSR200

4

______________________________________________________________



Byte Definitions


The table below shows the definition of the module



Consumed output byte
Bit

High

Low

00

K1 energized

K1 de-energized

01

K2 energized

K2 de-energized

02

Reserved Reserved

03

Reserved Reserved

04

Reserved Reserved

05

Reserved Reserved

06

Reserved Reserved

07

Reserved Reserved




Produced Input bytes
Input byte 1
: Configuration and status of MSR210 / MSR211
Bit

High

Low

00

Device ready

Monitoring active

01

Interrupt of any input

All inputs valid

02

Cross loop detected

No cross loop

03

Automatic reset

Supervised reset

04

Relay-output active (Safety system)

Relay-output not active (Safety system)

05

EDM dynamic

EDM static

06

EDM-loop open

EDM-loop closed

07

Internal fault or no basic module
connected

No internal fault and basic module
connected



Input-byte2: Status of Inputs of basic module and extension modules 1, 2 and 3
Bit

High

Low

00

Basic module, input 1 interrupted

Basic module, input 1 valid

01

Basic module, input 2 interrupted

Basic module, input 2 valid

02

Extension module 1, input 1
interrupted

Extension module 1, input 1 valid (or
module not existent)

03

Extension module 1, input 2
interrupted

Extension module 1, input 2 valid (or
module not existent)

04

Extension module 2, input 1
interrupted

Extension module 2, input 1 valid (or
module not existent)

05

Extension module 2, input 2
interrupted

Extension module 2, input 2 valid (or
module not existent)

06

Extension module 3, input 1
interrupted

Extension module 3, input 1 valid (or
module not existent)

07

Extension module 3, input 2
interrupted

Extension module 3, input 2 valid (or
module not existent)