Figure 2.1 XM Modules with Separate Power Connections
Any limited power
source that satisfies
the requirements
specified below
Power Supply Requirements
XM Power Supply Requirements
Protection
Listed Class 2 rated supply, or
Fused* ITE Listed SELV supply, or
Fused* ITE Listed PELV supply
Output Voltage
24 Vdc ± 10%
Output Power
100 Watts Maximum (~4A @ 24 Vdc)
Static Regulation
± 2%
Dynamic Regulation
± 3%
Ripple
< 100mVpp
Output Noise
Per EN50081-1
Overshoot
< 3% at turn-on, < 2% at turn-off
Hold-up Time
As required (typically 50mS at full rated load)
* When a fused supply is used the fuse must be a 5 amp, listed, fast acting fuse such as