RTD Current Source Value

Isolation

(XM-362 only)

Common Mode Input Voltage

(XM-361 only)

Input Impedance

1.004 mA ±1%

Up to 250 volts of isolation for each input

±3 Volts

XM-361: 1 Mohm voltage input
XM-362: 10 k voltage input

Outputs

4-20 mA Outputs

Accuracy

Isolation

Two isolated banks of three outputs (one
per channel)
600 ohm max load

±1% of full scale max
±0.2% of full scale typical

250 Volts

Indicators

6 LEDs Module Status - red/green

Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Channel 3 Status - yellow/red
Channel 4 Status - yellow/red
Channel 5 Status - yellow/red
Channel 6 Status - yellow/red

Signal Conditioning

Accuracy

Resolution

Low Pass Filter

Sampling Rate

Measured Units


C Thermocouples: ±3°C (±6°F) or 0.6% of
full scale, whichever is greater
E, J, K, N, T Thermocouples: ±1°C (±2°F) or
0.6% of full scale, whichever is greater
B, R, S Thermocouples: ±4°C (±7°F) or 0.6%
of full scale, whichever is greater
Platinum & Nickel RTDs (3-wire only): ±1°C
(±2°F) or 0.6% of full scale, whichever is
greater
Copper RTDs (3-wire only): ±7°C (±13°F) or
5% of full scale, whichever is greater

RTDs and Thermocouples: 0.025% of
temperature range

User configurable for the measurement and
rate of change value from each channel

200 Hz

°F
°C

XM-361/362 Technical Specifications

Product Feature

Specification

Advertising