Publication GMSI10-UM008D-EN-P - August 2010
31
Connecting a 2-Wire RTD
Figures 2.20 to 2.25 show the wiring of 2-wire RTDs to the terminal base unit
of the XM-361 module.
Figure 2.20 2-wire RTD to Channel 1 Wiring
ATTENTION
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-361
terminal base and not at the field device. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments on page 18).
TYPICAL WIRING FOR 2-WIRE RTD TO
X M -3 61 T E M P E R A T U R E M O D U LE C H A N N E L 1
3
19
20
41
RTD +
2-wire
RTD
RTD -
Shield