To 2.25 sho, Connecting a 4-wire rtd – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 42

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

34

Figure 2.25 2-wire RTD to Channel 6 Wiring

Connecting a 4-Wire RTD

Figures 2.26 to 2.31 show the wiring of 4-wire RTDs to the terminal base unit
of the XM-361 module. Wiring of a 4-wire RTD is exactly the same as the
3-wire RTD with one wire left open.

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-361
terminal base and not at the field device. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments on
page 18).

TYPICAL WIRING FOR 2-WIRE RTD TO

X M -3 61 T E M P E R A T U R E M O D U LE C H A N N E L 6

13

29
30

43

RTD +

2-wire
RTD

RTD -

Shield

Advertising
This manual is related to the following products: