Publication GMSI10-UM008D-EN-P - August 2010

54

Sets the relay activation logic.

A or B - Relay is activated when either Alarm A or

Alarm B meets or exceeds the selected Alarm
Status
condition(s).

A and B - Relay is activated when both Alarm A

and Alarm B meet or exceed the selected Alarm
Status
condition(s).

A Only - Relay is activated when Alarm A meets

or exceeds the selected Alarm Status
condition(s).

Options: A only

A or B
A and B

Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select an alarm only in Alarm A.

Options: Channel 1 value alarm

Channel 2 value alarm
Channel 3 value alarm
Channel 4 value alarm
Channel 5 value alarm
Channel 6 value alarm
Channel 1 rate alarm
Channel 2 rate alarm
Channel 3 rate alarm
Channel 4 rate alarm
Channel 5 rate alarm
Channel 6 rate alarm
Channel 1 difference alarm
(Ch1 minus Ch6)
Channel 2 difference alarm
(Ch2 minus Ch1)
Channel 3 difference alarm
(Ch3 minus Ch2)
Channel 4 difference alarm
(Ch4 minus Ch3)
Channel 5 difference alarm
(Ch5 minus Ch4)
Channel 6 difference alarm
(Ch6 minus Ch5)

Note: You can only select an alarm
that is enabled.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Activation Logic

Logic

XM Configuration
Utility

EDS File

Alarm A/B

Alarm
Identifier
A/B