Publication GMSI10-UM008D-EN-P - August 2010

53

Relay Parameters

Parameter Name

Description

Options/Comments

Number (XM Serial Configuration
Utility only)

Sets the relay to be configured in the XM Serial
Configuration Utility.

The relays are either relays on the
Expansion Relay module when it is
connected to the XM-361 or XM-362
or virtual relays.

Virtual relays are non-physical relays.
Use them when you want the effect of
the relay (monitor alarms, delay, and
change status) but do not need an
actual contact closure. For example, a
PLC or controller monitoring the relay
status.

Note: The Relay Installed parameter
indicates whether a relay is a virtual
relay or a physical relay on a module.

Name (XM Serial Configuration
Utility only)

A descriptive name to help identify the relay in the
XM Serial Configuration Utility.

Maximum 18 characters

Enable

Enable/disable the selected relay.

Note: The Relay Current Status is set to "Not
Activated" when the relay is disabled. See page 62.

Controls whether the relay must be explicitly reset
after the alarm subsides.

Activation Delay

Enter the length of time for which the Activation
Logic
must be true before the relay is activated. This
reduces nuisance alarms caused by external noise
and/or transient vibration events.

Enter a value from 0 to 25.5 seconds,
adjustable in increments of 0.1
seconds.

Default is 1 second

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled

XM Configuration
Utility

EDS File

Latching

Latching
Option

XM Configuration
Utility

EDS File

Check means
latching (relay must
be explicitly reset)

Latching

Clear means
non-latching (relay
is reset once the
alarm condition has
passed)

Nonlatching