Inputs

Channels

Supported Thermocouple Types

Supported RTD Types

1 to 6 RTD or thermocouple transducer
signals, user configurable
XM-361 accepts RTD and thermocouple
inputs
XM-362 accepts thermocouple inputs only

100 ohm 2-wire & 3-wire Platinum
(alpha = 0.00385):
-40 to 660°C (-40 to 1220°F)

200 ohm 2-wire & 3-wire Platinum
(alpha = 0.00385):
-40 to 453°C (-40 to 847°F)

100 ohm 2-wire & 3-wire Platinum
(alpha = 0.003916):
-40 to 660°C (-40 to 1220°F)

200 ohm 2-wire & 3-wire Platinum
(alpha = 0.003916):
-40 to 443°C (-40 to 829°F)

250 ohm 2-wire & 3-wire Platinum
(alpha = 0.00392):
-40 to 389°C (-40 to 732°F)

100 ohm 2-wire & 3-wire Nickel
(alpha = 0.00618):
-40 to 180°C (-40 to 356°F)

120 ohm 2-wire & 3-wire Nickel:
(alpha = 0.00672):
-40 to 439°C (-40 to 822°F)

10 ohm 2-wire & 3-wire Copper:
(alpha = 0.00427):
-40 to 260°C (-40 to 500°F)

XM-361/362 Technical Specifications

Product Feature

Specification

Type Range C°

Range F°

B

0°C to 1810°C

(32°F to 3290°F)

C

0°C to 1316°C

(32°F to 2400°F)

E

5°C to 284°C

(41°F to 543°F)

J

0°C to 364°C

(32°F to 687°F)

K

-40°C to 484°C

(-40°F to 903°F)

N

-40°C to 620°C

(-40°F to 1148°F)

R

-40°C to 1760°C (-40°F to 3200°F)

S

-40°C to 1760°C (-40°F to 3200°F)

T

-40°C to 379°C

(-40°F to 714°F)