Publication GMSI10-UM014D-EN-P - May 2010

Configuration Parameters 55

Alarm Parameters

The Alarm parameters control the operation of the alarms (alert and danger
level) and provide alarm status. The Absolute Shaft module provides nine
alarms. Each alarm is permanently associated with a corresponding
measurement (for example, Channel 1 Shaft Relative Overall alarm, Channel 2
Case Absolute Overall alarm, and so on). Use the parameters to configure
which measurement the alarm is associated with, as well as the behavior of the
alarm.

Trigger Hysteresis

The amount of hysteresis around the trigger
threshold. In Auto Trigger mode, the value entered is
a percentage of the peak-to-peak input signal. This
value can range from 0 to 50%.

In Manual Trigger mode, the value entered is a
voltage level. The hysteresis voltage is added to or
subtracted from the threshold voltage to determine
the hysteresis range. The minimum value is 0.12
volts.

% in Auto Trigger mode
Volt in Manual Trigger mode

Trigger Threshold

The signal level to be used as the trigger value when
in Manual Trigger mode.

Enter a value from +16 to -16 volts dc.

Note: This value is not used in Auto
Trigger mode.

Trigger Slope

The input signal slope to be used as the trigger value
when in Manual Trigger mode.

Options: Positive

Negative

Note: This value is not used in Auto
Trigger mode.

Tachometer Signal Processing Parameters

Parameter Name

Description

Values/Comments

Alarm Parameters

Parameter Name

Description

Values/Comments

Alarm (XM Serial Configuration
Utility only)

Sets the alarm to be configured in the XM Serial
Configuration Utility. Each alarm is associated with a
particular measurement.

Options: Ch. 1 SR (shaft relative)

Overall
Ch. 2 CA (case absolute)
Overall
Ch. 1 SR 1X Mag
Ch. 2 CA 1X Mag
Shaft Absolute Overall
Shaft Absolute 1X Mag
Ch. 1 DC Bias
Ch. 2 DC Bias
Speed

Name (XM Serial Configuration
Utility only)

A descriptive name to identify the alarm in the XM
Serial Configuration Utility.

Maximum 18 characters