Trusted

TM

CS300 Bridge Module

Issue 01 Apr 08

PD-8162

12

The four backplane jumpers 0,1,2,3 (A,B,C) represent the binary address bits 1,2,4 & 8 respectively. A
fitted jumper signals a binary digit ‘1’. The address is set to between 2 and 8. On the first CS300
chassis (containing the CS300 Bridge Modules), fit jumper 1 (A,B,C) to represent Trusted

TM

address

'2'. The jumpers on all three sets must be set to the same address. Leave the jumpers as they were on
the other CS300 chassis. It is usual to attach the chassis with address 2 to the first Expander Interface
Adapter socket, for both Trusted

TM

chassis and CS300 chassis. This makes the software configuration

easier.