3.8. Module – pi626 / pi726 (digital output module)

DESCRIPTION
This definition will open a single PI626 or PI726.

OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS

2-29

Logical chassis and slot number where the CIO_DO is located.

SLOT

1-15

PHYSICAL MODULE:
RACK 1: (DO)

32 BOOLEAN outputs

RACK 2: (DIAG)

2 INTEGER inputs

Word 1 Diagnostic bits

bit 0

Slice A

=1

slice is not responding or there is an error

=0

slice is responding

bit 1

Slice B

=1

slice is not responding or there is an error

=0

slice is responding

bit 2

Slice C

=1

slice is not responding or there is an error

=0

slice is responding

bit 3

Module offline or missing

=1

offline or missing

=0

online

bit 4

Single slot hot repair

=1

in progress

=0

not in progress

bit 5

Discrepancy errors

=1

faults detected

=0

no faults detected

bit 6

LFD faults

=1

faults detected

=0

no faults detected