Having added all the chassis in the system, the next step is to insert modules. For each module, right-
click on the appropriate chassis slot. Select the module from the list.

Figure 14 CS300 Modules

On left-clicking the module, the module options are displayed.

Figure 15 Module Options

If the module has been allocated a Hot Repair partner slot, so that the partner module can take over on
failure, then check the Hot Repair Module option. The configurator will automatically allocate the next
appropriate slot, but this may be edited. There is no need to insert a module for the hot repair slot; the
configurator will add this automatically There is also no need to edit the options for the hot repair
module. The hot repair partnership is set up using the interlinking ribbon cable between the modules.
The ‘Mode’ is included for PI727 modules which can be set to 3-2-1 or 3-2-0 operation..
For output modules, an input module may be configured to monitor the outputs as a diagnostic
feedback. Where this is required, check the Enable Monitor option and select the chassis and slot of
the input module. For analogue output modules, also select the monitor channel.
With monitoring enabled, it is possible to add LFD testing. Complete testing is only possible with two
online output cards (in a hot repair configuration).
To allow the system to run with a module absent, check ‘Simulate’.
Ensure that the options selected are as configured in the original application.