Figure 9 cs300 main chassis, Figure 10 chassis connection, Figure 11 connected chassis – Rockwell Automation CS300 Trusted CS300 Bridge Module User Manual

Page 14: Trusted, Cs300 bridge module

Advertising
background image

Trusted

TM

CS300 Bridge Module

Issue 01 Apr 08

PD-8162

14

The first chassis to be created is a CS300 8162. This includes the bridge modules in place of the
CS300 processors. Choose typeCS300 8162 and select a logical chassis number. This chassis
number will define the switch configuration described in section 2.3.

Figure 9 CS300 Main Chassis

The chassis should then be allocated to the Trusted

TM

Expander Interface module. Left-click on the left

or right end of the CS300 8162 chassis to open the Chassis Connection dialog. Select the slot number
of the left-hand Expander Interface module.

Figure 10 Chassis Connection

On closing this dialog, the CS300 8162 chassis should have a blue flash symbol on the left. The right
hand side shows the chassis address as:
< Trusted

TM

expander Interface slot> - <Expander socket number> - <CS300 chassis number>

Figure 11 Connected Chassis

Left-click on the left or right end of the CS300 8162 chassis to open the Chassis Connection dialog
again. The ‘Jumper Config’ button now demonstrates how to set the backplane jumpers.

Advertising