Module – 8162 (bridge module), Trusted, Cs300 bridge module – Rockwell Automation CS300 Trusted CS300 Bridge Module User Manual

Page 18

Advertising
background image

Trusted

TM

CS300 Bridge Module

Issue 01 Apr 08

PD-8162

18

3.3. Module – 8162 (Bridge Module)

DESCRIPTION

This definition provides module status for a 8162 primary chassis expansion interface module that
provides an expansion bridge from Trusted

TM

to CS300 systems.

The logical module accounts for the 3 physical modules FCR-A, FCR-B and FCR-C.

OEM PARAMETERS:
OEM parameter Valid numbers Description
CHASSIS

2-29

Logical chassis number allocated to the primary CS300 chassis in
which the 8162 modules are placed.

SLOT

16

Logical slot within the Primary CS300 chassis by which the Trusted

TM

system identifies the 8162 module. This cannot be configured.

PHYSICAL MODULE:
RACK 1: [STATUS] - 6 BOOL Inputs

Variable 1:

TRUE = Logical module responding

Variable 2:

TRUE = FCR-A faulted or not responding

Variable 3:

TRUE = FCR-B faulted or not responding

Variable 4:

TRUE = FCR-C faulted or not responding

RACK 2: [INFO] - 12 ANALOGUE Inputs

Word 1:

FCR-A fault code (see note 1)

Word 2:

FCR-B fault code (see note 1)

Word 3:

FCR-C fault code (see note 1)

Word 4:

FCR-A hot-link error count

Word 5:

FCR-B hot-link error count

Word 6:

FCR-C hot-link error count

Word 7:

FCR-A IML own-link error count

Word 8:

FCR-A IML down-link error count

Word 9:

FCR-A IML up-link error count

Word 10:

FCR-B IML own-link error count

Word 11:

FCR-B IML down-link error count

Word 12:

FCR-B IML up-link error count

Word 13:

FCR-C IML own-link error count

Word 14:

FCR-C IML down-link error count

Word 15:

FCR-C IML up-link error count


[Note 1 - Fault Codes]

0

: No fault

1

: Local backplane fault

2

: Local expansion bus fault

3

: Common fault (applies to both local backplane and expansion busses)

Advertising