Module – pi632 / pi732 (analogue input module), Trusted, Cs300 bridge module – Rockwell Automation CS300 Trusted CS300 Bridge Module User Manual

Page 20

Advertising
background image

Trusted

TM

CS300 Bridge Module

Issue 01 Apr 08

PD-8162

20

3.5. Module – pi632 / pi732 (analogue input module)

DESCRIPTION
This definition will open a single PI632 or PI732.

OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS

2-29

Logical chassis and slot number where the CIO_AI is located.

SLOT

1-15


PHYSICAL MODULE:
RACK 1: (AI)

16 INTEGER inputs

RACK 2: (DIAG)

2 INTEGER inputs

Word 1 Diagnostic bits

bit 0

Slice A

=1

slice is not responding or there is an error

=0

slice is responding

bit 1

Slice B

=1

slice is not responding or there is an error

=0

slice is responding

bit 2

Slice C

=1

slice is not responding or there is an error

=0

slice is responding

bit 3

Module offline or missing

=1

offline or missing

=0

online

bit 4

Single slot hot repair

=1

in progress

=0

not in progress

bit 5

Discrepancy errors

=1

faults detected

=0

no faults detected

Word 2 Slot number of active module

RACK 3: (FAULTS)

1 INTEGER inputs

Word 1 Discrepancy errors, channels 1-16 (bit 0 = channel 1)