Trusted, Cs300 bridge module – Rockwell Automation CS300 Trusted CS300 Bridge Module User Manual
Page 27
Advertising
Trusted
TM
CS300 Bridge Module
Issue 01 Apr 08
PD-8162
27
RACK 3: (FAULTS)
4 INTEGER inputs
Word 1 Discrepancy errors, channels 1-16 (bit 0 = channel 1)
Word 2 Discrepancy errors, channels 17-32 (bit 0 = channel 17)
Word 3 LFD errors, channels 1-16 (bit 0 = channel 1)
Word 4 LFD errors, channels 17-32 (bit 0 = channel 17)
NOTES:
Discrepancy errors will only be checked if the DO module has a configured DI monitor module.
Discrepancy errors indicate a difference between the output value on a DO and the voted input value
on the DI monitor.
Advertising