3.7. Module – pi616_5 / pi616_9 / pi716 / pi717 (digital input module)

DESCRIPTION
This definition will open a single PI616 type 5 or PI616 type 9 or PI716 or PI717.

OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS

2-29

Logical chassis and slot number where the module is located.

SLOT

1-15


PHYSICAL MODULE:
RACK 1: (DI)

32 BOOLEAN inputs

RACK 2: (DIAG)

2 INTEGER inputs

Word 1 Diagnostic bits

bit 0

Slice A

=1

slice is not responding or there is an error

=0

slice is responding

bit 1

Slice B

=1

slice is not responding or there is an error

=0

slice is responding

bit 2

Slice C

=1

slice is not responding or there is an error

=0

slice is responding

bit 3

Module offline or missing

=1

offline or missing

=0

online

bit 4

Single slot hot repair

=1

in progress

=0

not in progress

bit 5

Discrepancy errors

=1

faults detected

=0

no faults detected

Word 2 Slot number of active module

RACK 3: (FAULTS)

2 INTEGER inputs

Word 1 Discrepancy errors, channels 1-16 (bit 0 = channel 1)

Word 2 Discrepancy errors, channels 17-32 (bit 0 = channel 17)