Specifications, opbx2 series power blocks, Power block programming information, Address number – Banner OMNI-BEAM Series User Manual

Page 2: Power block output status, Module mode

Advertising
background image

Banner Engineering Corp., 9714 10th Ave. No., Minneapolis, MN 55441 Telephone: (763) 544-3164 FAX (applications): (763) 544-3573

Specifications, OPBX2 Series power blocks

Models:

OPBX2 (attached 6-1/2 foot cable), or OPBX2QD (5-pin

minifast™ QD; requires Banner XQDC12 Quick Disconnect cable).

Supply voltage:

+9 to 12V dc; 80 mA per sensor at 12V dc (power

block output conducting).

Clock requirements:

Use APC SPX-CLK Series clock module,

available from APC.

SPX-CLK10K (10 kilohertz)

SPX-CLK64K (64 kilohertz)

SPX-CLK32K (32 kilohertz)

SPX-CLK100K (100 kilohertz)

One clock module is required per stand-alone network.

Wiring information:

Use only Seriplex-compatible cable.

Standard OPBX2 model has a 6-1/2 foot attached unterminated

cable.

QD model OPBX2QD requires Banner XQDC12 mating QD cable.

QD cable length is 12 feet; 5-pin minifast™ female sensor connector

on one end with other end unterminated.
Unterminated sensor extension cable (XECS Series) is available.
For bus cable, use Banner XECT Series cable.
Banner PHOTOBUS™ BUS DEPOT™ junction boxes provide a

convenient means of connecting PHOTOBUS™ sensors to a SERI-

PLEX

®

bus. Model BD6T1 (product data sheet 34146) enables parallel

connection of up to six I/O devices on a continuing bus. Model BD2T2

enables parallel connection of two bus branches or two I/O devices on

a continuing bus (see product data sheet 34437).

Programming cable:

Model XPC1A, available from Banner.

Jumper plug is model XPJ1, and is supplied with the power block.

See discussion at left for more information.

Programming is done via the APC Hand-held Programmer.

OPBX2 Series Control Byte

Module mode: 0 = stand-alone, 1 = host processor

Unused (must be set to 1)

Unused (must be set to 1)

Unused, setting is ignored

Unused, setting is ignored

Unused, setting is ignored

ALARM

* output (B) status: set to 0

LOAD

* output (A) status: set to 0

7 6 5 4 3 2 1 0

Bits:

1 1

*OMNI-BEAM Standard sensor heads. When E Series sensor heads are used, the

normally open LOAD output from the sensor head appears simultaneously on both

A and B power block outputs.

1 1

Figure 3. OPBX2 Series control byte

Connection to a stand-alone network

OMNI-BEAM OPBX2 Series PHOTOBUS™ Power Block

Modules are connected in parallel with each other (and with the

devices they are to control) on a Seriplex network. Possible network

configurations include ring, loop-back, star, or bus. Power blocks

are available with either attached cable or a built-in QD (Quick

Disconnect) connector. QD models require Banner XQDC Series

cable, sold separately.

Power block programming information

The programming information presented in this data sheet is in

addition to the programming procedure details given in the Pro-

gramming Seriplex™ I/O Modules section of the APC Seriplex

Programmable Control System Instruction Manual provided with

the APC hand-held programmer. Read and understand both the APC

manual and the information below before attempting to program

the OPBX2 Series Power Block.
OPBX2 Series Power Blocks are programmed, by the user, for

three attributes (details below). The APC hand-held programmer

connects to the programming port of the power block using a pro-

gramming cable (model XPC1A, available from Banner, see Figure

2 for connection information). Programming is typically done at

initial system setup, and may be done either before or after the

power block is wired into the Seriplex network. Since EEPROMs

retain their programmed information in spite of power failures, they

need be reprogrammed only if the usage of the sensor within the

network changes. The three programmable attributes are:

Address number:

The load and alarm outputs from Standard

OMNI-BEAM Sensor heads are separate and distinct, and are

addressed separately as channel A (load) and channel B (alarm).

If the alarm signal is not required, assign channel B to an unused

address. When E Series Sensor Heads are used, the normally open

load output from the sensor head appears simultaneously on both

power block outputs (A and B). Addresses are decimal values in

the range of 001 through 255, and need not be assigned in numerical

order. (NOTE: Care should be taken when choosing addresses.

The Seriplex

®

system will logically "OR" signals with the same

address. See Seriplex

®

literature for more information.)

Power block output status:

Bits 6 and 7 of the control byte

(Figure 3) are used to configure channel B and channel A power

block outputs (respectively). Setting these bits to "1" inverts the

signal within the power block. It is recommended that these bits

be set to "0". Signal inversions may instead be performed via a

dip switch inside the sensor head.

Module mode:

Bit 0 in the control byte (Figure 3) is used to

select the power block's mode of operation. Set this bit to "0" if

there is no host processor connected (stand-alone mode). If output

data will be read from the data line as set by a host processor , set

this bit to "1".
Bits 1 and 2 are test bits which are not used in normal opera-

tion, and must be set to "1".

Figure 2.

Power block with jumper plug in operating posi-

tion (left), and with jumper plug removed and program-

ming cable attached (right); APC hand-held programmer in

background.